Part B - Verifications and approval requirements
87
6 Submarine cables
6.1 Preliminary remarks
The cables and accessories used must be state of the art and meet the requirements of the
relevant standards in each case (selection see below) or their suitability must have been
proven by comparable tests and they must be suitable for the particular operating conditions/
applications.
Reference is made to the specifications of the Spatial Offshore Grid Plan (BFO) in the current
version. Only one approval is granted for the cabling within the wind farm and the power out
put cable.
6.2 Technical codes of practice
6.2.1 Cabling within the wind farm
For test requirements and suitability certificates, the following technical codes of practice in
their current version must be complied with in relation to alternating current transmission us
ing plastic-insulated power cables (energy distribution cables):
DIN VDE 0276-620 (VDE 0276-620)
IEC 60502-2 Power cables with extruded insulation and their accessories for rated
voltages from 1 kV (U m = 1.2 kV) up to 30 kV (U m = 36 kV) - Part 2:
Cables for rated voltages from 6 kV (U m = 7.2 kV) up to 30 kV (U m = 36 kV)
DIN VDE 0278-629-1 (VDE 0278-629-1)
IEC 60502-4 Power cables with extruded insulation and their accessories for rated
voltages from 1 kV (U m = 1.2 kV) up to 30 kV (U m = 36 kV) - Part 4:
Test requirements on accessories for cables with rated voltages from
6 kV (U m = 7.2 kV) up to 30 kV (U m = 36 kV)
DIN EN 61442 (VDE 0278-442)
IEC 61442 Test methods for accessories for power cables with rated voltages
from 6 kV (U m = 7.2 kV) up to 30 kV (U m = 36 kV)
6.2.2 Connection to the power grid
6.2.2.1 Alternating current transmission
For test requirements and suitability certificates, the following technical codes of practice in
their current version must be complied with for alternating current transmission using plastic-
insulated low-voltage, medium-voltage and high-voltage cables:
DIN VDE 0276-632 (VDE 0276-632)
IEC 60840 Power cables with extruded insulation and their accessories for rated
voltages above 30 kV (U m = 36 kV) up to 150 kV (U m = 170 kV) - Test
methods and requirements
DIN IEC 62067 (VDE 0276-2067)
IEC 62067 Power cables with extruded insulation and their accessories for rated
voltages above 150 kV (U m = 170 kV) up to 500 kV (U m = 550 kV) - Test
methods and requirements